    Battery vs. generator emergency lighting: How testing differs

    Battery units are tested one at a time: a 30-second test every month and a 90-minute test every year under NFPA 101, with written records. Generator-fed emergency lighting is tested through the generator program under NFPA 110, which runs on its own weekly and monthly schedule.

    Emergency lighting can get its backup power from two places: a battery in or near each light, or a generator that picks up the load when normal power fails. Many buildings have both.

    The code treats them differently. Knowing which kind you have tells you which tests apply and what records your inspector will ask for.

    What every system has to do

    NFPA 101, the Life Safety Code, sets the same performance goal no matter where the power comes from:

    • Emergency lighting must last at least 90 minutes after normal power fails (Section 7.9.2.1)
    • It must start lighting the path of egress within 10 seconds (Section 7.9.1.3)
    • It must deliver a minimum level of light along the path of egress for the full 90 minutes

    The sections in this article come from the 2012 edition, which CMS uses for healthcare facilities. The Texas State Fire Marshal's Office uses the 2021 edition, and Austin and San Antonio adopt the International Fire Code with local amendments. Ask your AHJ which edition applies to your building.

    Battery-powered lights: every unit, every month

    Battery units include wall packs, "bug-eye" lights and exit signs with battery backup. Each one is its own small system, so each one is tested on its own.

    NFPA 101 Section 7.9.3.1.1 asks for:

    • A functional test every month, for at least 30 seconds
    • A test every year, for at least 90 minutes
    • Written records of the tests

    Battery exit signs follow the same rules. Two things trip teams up:

    • The test button may not test the battery. A Minnesota Department of Health surveyor guide warns that on some older units, the button may only test the lamps.
    • Thirty seconds doesn't prove 90 minutes. A battery can pass the monthly test and still fail the annual one. Only the 90-minute test checks full duration.

    Generator-backed lights: the generator gets tested

    When a generator powers emergency lighting, NFPA 101 Section 7.9.2.4 sends you to NFPA 110, the standard for emergency and standby power systems. Testing then centers on the generator and the transfer switch.

    Under NFPA 110 (2010 edition, as cited in a Minnesota Department of Health surveyor guide), that includes:

    • A weekly inspection of the generator
    • A monthly run of at least 30 minutes under load
    • A monthly operation of each transfer switch
    • For Level 1 systems, a longer test every 36 months
    • Written records of all of it

    Hospitals have extra rules on top of this through NFPA 99, such as running the generator 12 times a year at 20 to 40 day intervals.

    A generator test shows the generator and transfer switch work. Ask your AHJ how they expect you to confirm the lights on those circuits come on, too.

    Buildings with both

    Many buildings use generator-fed lighting in some areas and battery units in others, such as a stairwell added later or a building without generator coverage. That means two testing programs and two sets of records.

    Start with an inventory: which lights are on battery, which are on the generator, and where each one is. Without that list, battery units are the ones that get missed.

    What surveyors find

    Records are where findings usually start. Surveyors look for dated proof that every battery unit got its monthly test and its full 90-minute annual test. Our guide to why emergency lights fail inspection covers the most common record gaps.

    Where automated testing fits

    For battery-powered lights, a computer-based self-testing system runs the monthly and annual tests on schedule and keeps the history of tests and failures. NFPA 101 permits this (Section 7.9.3.1.3).

    The ABB Emergi-Lite® Nexus Pro system is a computer-based option for battery-powered emergency lights, exit signs and combo units. Emergi-Lite's central and mini inverter systems can also use Nexus® Pro testing. Nexus Pro doesn't test your generator. If your building uses both, Nexus Pro handles the battery side and your generator program stays as it is.

    Key takeaways

    • Battery units are tested one by one: 30 seconds monthly, 90 minutes yearly, with records
    • Generator-fed lighting follows NFPA 110: weekly inspections, monthly load runs and transfer switch tests
    • Buildings with both need an inventory and two sets of records
    • Ask your AHJ which edition applies and how they want records presented