    Exit sign testing: What's required and what gets missed

    Exit signs with battery backup are tested like emergency lights under NFPA 101: a 30-second test every month and a 90-minute test every year, with written records. Photoluminescent and tritium signs have no battery, so they need different checks, covered below.

    The Texas State Fire Marshal's Office lists failure to maintain emergency lights and lighted exit signs among the most common violations in its yearly inspection report. Here's what the codes ask for, and where teams fall short.

    The monthly check

    NFPA 101, the Life Safety Code, asks for every exit sign to be visually inspected at least every 30 days to confirm its light source is working (Section 7.10.9.1). A computer-based system that monitors the signs can take the place of that walk.

    If a sign has battery backup, it's also tested like an emergency light (Section 7.10.9.2):

    • A functional test every month, for at least 30 seconds
    • A test every year, for at least 90 minutes
    • Written records of the tests

    The sections here come from the 2012 edition, which CMS uses for healthcare facilities. The Texas State Fire Marshal's Office uses the 2021 edition, and Austin and San Antonio adopt the International Fire Code with local amendments. Ask your AHJ which code and edition apply to your building.

    What OSHA adds

    For workplaces, OSHA's exit route rules (29 CFR 1910.37(b)) cover the sign itself:

    • Each exit must be marked with an "Exit" sign
    • Where the way to an exit isn't obvious, signs must point the way
    • Doors that could be mistaken for an exit must be marked "Not an Exit" or with their actual use
    • Signs must be lit to at least five foot-candles by a reliable light source, or be self-luminous or electroluminescent at 0.06 footlamberts or more
    • "Exit" letters must be at least six inches high

    Three kinds of signs, three things to watch

    • Signs with battery backup. The most common type. The monthly and annual tests apply to each one. A sign that stays lit on normal power can still have a dead battery, which only a test will show.
    • Photoluminescent signs. These glow from light they absorb. NFPA 101 requires the sign face to be continually lit by its charging light while the building is occupied (Section 7.10.7.2). If the lights in that area are turned off or changed, the sign can stop working.
    • Self-luminous (tritium) signs. These glow without power, but they don't last forever. The NRC says a sign that no longer lights all its letters may have reached the end of its working life. They also can't go in the trash: tritium signs have to go back to a licensed company such as the manufacturer, and the transfer must be reported. In Texas, the Department of State Health Services regulates this in place of the NRC.

    What gets missed

    • Signs that work on normal power but fail on battery. The Town of Prosper, Texas lists exit and emergency lights that don't run on battery among its top reasons inspections fail.
    • Missing records. A sign can pass and still lead to a finding if there's no written record of the test.
    • Directional signs. After a remodel or a new wall, the path to the exit can change, and a sign that used to be enough may not be.
    • Blocked signs. Shelving, banners and holiday decorations can hide a sign that's working fine.

    Where automated testing fits

    A computer-based self-testing system runs the monthly and annual tests on battery-backed exit signs and emergency lights, and keeps a history of tests and failures. NFPA 101 permits this.

    The ABB Emergi-Lite® Nexus Pro system is a computer-based option that covers exit signs, combo units and emergency lights. It flags a failed sign as soon as a test finds it, so you don't learn about it on inspection day. Signs still need someone to look at them for damage and blocked views.

    Key takeaways

    • Look at every exit sign at least every 30 days, or use a system that monitors them
    • Battery-backed signs get the same 30-second and 90-minute tests as emergency lights
    • Photoluminescent signs need their charging light; tritium signs expire and need proper disposal
    • Keep written records, and recheck directional signs after any layout change